Back to top
08045803208
Send SMS Send Inquiry


      Minilec Phase Failure Relays ALV D2

      Minilec Phase Failure Relays ALV D2
      Minilec Phase Failure Relays ALV D2

      Minilec Phase Failure Relays ALV D2 Specification

      • Dielectiric Strength
      • 2kV AC for 1 minute between terminal & enclosure
      • Power Consumption
      • 2VA (approx.)
      • Coil Voltage
      • 415V AC
      • Coil Power
      • 2VA
      • Protect Feature
      • Phase Failure, Sequence, and Unbalance Protection
      • Contact Material
      • Silver Alloy
      • Working Temperature
      • -10C to +50C
      • Contact Form
      • 1 Changeover (SPDT)
      • Contact Resistance
      • 100 m (initial)
      • Mechanical Life
      • 10 operations
      • Ambient Temperature
      • -10C to +55C
      • Product Type
      • Phase Failure Relay
      • Insulation Resistance
      • >100 M at 500 VDC
      • Theory
      • Electromagnetic Relay
      • Usage
      • Industrial protection of three-phase motors and equipment
      • Contact Load
      • 5A at 250V AC/30V DC
      • Operate Time
      • Less than 200 ms
      • Terminal Type
      • Screw type
      • Rated Voltage
      • 415V AC
      • Supply Terminal
      • L1-L2-L3
      • Size
      • DIN Rail Mount
      • Color
      • White and Blue
      • Dimension (L*W*H)
      • 77 x 22.5 x 110 mm
      • Weight
      • Approx. 100g
      • Humidity
      • Up to 95% RH (non-condensing)
      • Phase Sequence
      • Protects against incorrect phase sequence
      • Minimum Load
      • 100mA at 5V DC
      • Output Type
      • Relay output
      • Standards Compliance
      • IS/IEC standards
      • Phase Unbalance Percentage
      • 50% max
      • Status Indication
      • LED indication for relay status
      • Reset Type
      • Automatic reset
      • Number of Poles
      • 1 Pole
      • Response Time
      • Less than 200 ms
      • Enclosure Material
      • Flame retardant polycarbonate
      • Mounting
      • DIN Rail Mountable
       
       

      About Minilec Phase Failure Relays ALV D2

      Minilec Phase Failure Relays

      OVERVIEW :-


      Phase Failure, Unbalance,

      Phase Sequence, under voltage,

      Over Voltage, Auto Reset,

      Fixed unbalance setting,

      Adjustable UV/OV settings,

      2 CO output relay

      TECHNICAL SPECIFICATION :-

      Supply Voltage


      System : 110 / 240 / 380 / 415 / 440 V AC ±20% 50 / 60 Hz

      Auxillary : 110 V (Fixed) or (220 - 230 - 240) or
      (380 - 415 - 440) V AC ±20% selectable

      Output Contacts : 2 CO

      Trip Setting(Volts)


      Phase Sequence : Yes

      Phase Unbalance : 40 V ±6 V (fixed)


      Under
      Voltage
      For 380-440V AC
      For 220-240V AC
      For 110 V AC
      line 80% to 95% (adjustable) of auxillary supply (±2% of set value)

      Over
      Voltage
      For 380-440V AC
      For 220-240V AC
      For 110 V AC
      line 105% to 120% (adjustable) of auxillary supply (±2% of set value)

      Trip Time Delay

      On Phase Failure : 3.5 secs. ± 1.5 sec

      On UV/OV : Less than 2 secs.

      Resetting Mode : Auto Reset

      Weight : 400 gms.

      Dimensions (mm)

      Overall (L x W x D) : 76 x 56.5 x 117.5

      Mounting (L x W) : 67 x 46 alt / 35 mm rail Mounting

      Note:

      Wherever not specified Contact Rating : 5A @ 230 V AC (resistive)

      * CE marked products available on request.

       ALV D2ALV D2

       

      APPLICATION :-

       

       

      Suitable for monitoring 3 Ph. System supply from MAINS & used by motor load 

      AC & R Chiller compressor motors.

      AHU Fan /Pump Motors

      Machinery using multiple small motors.

      MAIN powers supply distribution panel board.

      DG Set application

      UPS

      Submersible Pumps

      Hoist & Crane


      Reliable Protection for Critical Equipment

      The ALV D2 Phase Failure Relay is designed to monitor and protect three-phase motors and equipment from phase-related faults. It prevents motor damage by quickly responding to failures, incorrect phase sequences, and unbalances, making it a trusted solution for industrial setups. High reliability and compliance with IS/IEC standards ensure long-term performance and safety.


      Efficient Performance and Easy Installation

      This relay offers speedy response in less than 200 milliseconds and automatic reset operation, minimizing downtime and ensuring seamless protection. Its screw-type terminals and convenient DIN rail mounting simplify installation for distributors, suppliers, and traders in India. LED status indication allows for straightforward monitoring, contributing to efficient maintenance.


      Durable Design with Superior Materials

      Encased in flame-retardant polycarbonate, the relay withstands tough conditions, including up to 95% relative humidity. With mechanical life rated for up to 10 operations, it promises lasting durability. Strong insulation resistance and advanced contact materials guarantee safe, reliable operation in industrial environments.

      FAQs of Minilec Phase Failure Relays ALV D2:


      Q: How does the ALV D2 Phase Failure Relay help protect industrial equipment?

      A: The ALV D2 Relay immediately detects phase failures, incorrect phase sequence, and excessive phase unbalance, protecting three-phase motors and equipment from downtime and potential damage.

      Q: What is the process for installing the ALV D2 relay?

      A: Install the relay on a DIN rail using screw-type terminals for L1, L2, and L3 supply connections. The compact dimensions fit standard distribution panels, making setup quick and convenient.

      Q: When does the relay respond to phase issues, and how is status indicated?

      A: The relay responds to phase failures or unbalances in less than 200 milliseconds. Its LED indicator displays the current relay status, allowing users to monitor for faults in real time.

      Q: Where can the ALV D2 relay be used?

      A: The ALV D2 relay is suitable for use in industrial locations to protect three-phase motors, compressors, and related equipment, especially where standards compliance and rapid fault detection are needed.

      Q: What are the key benefits of automatic reset in this relay?

      A: Automatic reset enables the ALV D2 to restore protection immediately after transient faults are resolved, reducing the need for manual intervention and minimizing equipment downtime.

      Q: Is the ALV D2 relay durable in harsh environments?

      A: Yes, it supports up to 95% humidity (non-condensing), operates between -10C to +50C, and features a flame-retardant polycarbonate enclosure, ensuring sustained performance in challenging industrial conditions.

      Q: What standards does the ALV D2 Phase Failure Relay comply with?

      A: The relay complies with IS/IEC standards, guaranteeing reliable performance, electrical safety, and quality assurance for industrial environments.

      Tell us about your requirement
      product

      Price:

      Quantity
      Select Unit

      • 50
      • 100
      • 200
      • 250
      • 500
      • 1000+
      Additional detail
      Mobile number

      Email

      More Products in Minilec Phase Failure Relays Category

      Minilec Phase Failure Relays HLV D2

      Minilec Phase Failure Relays HLV D2

      Weight : Approx. 120 g

      Contact Resistance : < 50 m

      Coil Voltage : 415V AC (direct sensing from supply voltage)

      Mechanical Life : Over 10 million operations

      Coil Power : < 2 VA

      Insulation Resistance : >= 100M at 500V DC

      Minilec Phase Failure Relays D1 HL S1

      Minilec Phase Failure Relays D1 HL S1

      Weight : Approx. 120g

      Contact Resistance : <50m

      Coil Voltage : Internal to supply voltage

      Mechanical Life : >10 Million Operations

      Coil Power : Low Power Consumption

      Insulation Resistance : >=100M at 500V DC

      Minilec Phase Failure Relays D2 VMR2

      Minilec Phase Failure Relays D2 VMR2

      Weight : 120g

      Contact Resistance : <50m

      Coil Voltage : 415V AC

      Mechanical Life : >1 million operations

      Coil Power : Approx 3VA

      Insulation Resistance : >100M at 500V DC

      Minilec Phase Failure Relays S2 VMR3

      Minilec Phase Failure Relays S2 VMR3

      Weight : Approx. 180 grams

      Contact Resistance : < 50 m (initial)

      Coil Voltage : Operates on system voltage (415V AC)

      Mechanical Life : 1 million operations

      Coil Power : Low power, integrated with relay

      Insulation Resistance : > 100 M at 500V DC