Cookie Img
Back to top
   Call Me Free Offline
Home » Products » Minilec Motor Protection Relay » Minilec » Minilec Motor and Pump Protection Relays SPG D2

Minilec Motor and Pump Protection Relays SPG D2

Minilec Motor and Pump Protection Relays SPG D2
Minilec Motor and Pump Protection Relays SPG D2
Product Code : SPG D2
Brand Name : Minilec
Product Description

Minilec Motor and Pump Protection Relays

 OVERVIEW :-


Phase Failure

Unbalance

Phase sequence

Overloading and Dry running Auto / Manual Reset

Adjustable current trip settings

Selectable overload characteristics

1CO/2CO output relay

TECHNICAL SPECIFICATION:- 

Supply Voltage

System : 100-120/220-240/380-440V AC ±20%

Auxillary : 110/240/380/415/440 V AC/ 24 V AC/DC ±20%, 50 / 60 Hz

Output Relay Contact : 1 CO (2 C0)

Input : From CTS

Trip Setting


Phase to phase unbalance : 50% of motor Current

Under current (Dry running) : 50%/75% of set current

Overload : Above 120% of set current (IDMTL)

UV/OV : N.A.

Trip Time Delay

On phase failure : 5.5 secs. ± 1.5 secs.

For overloading : As per selectable inverse time Characteristics
2 / 5 secs (10 secs.)

UV/OV RP : N.A.

Resetting : Auto / Manual / Remote

Approx Weight : 425 gms.

Dimensions (mm)

Overall (L x W x D) : 76 x 56.5 x 117.5

Mounting (L x W) : 67 x 46 alt / 35 mm rail Mounting

Note:

Wherever not specified Contact Rating : 5A @ 230 V AC (resistive)

Selection Chart For CTS Times full Load Current
S2 CTS1 S2 CTS1

 CONNECTION DIAGRAM:-

Timing/ Relay logic Diagram

Electrical Connection Diagram

SPG D2 SPG D2

APPLICATION :-

 Suitable for Panels in Following Apllications:


Submersible Pump Control Panels.

Air Handling Unit Fans.

Belt Conveyor Motor panels for zero speed sensing.



JAIN ELECTRICALS & ENGINEERS

Contact Us

( *represents compulsory fields )

Tips on getting accurate quotes. Please include product name, order quantity, usage, special requests if any in your inquiry.